| Title: | 
        
            | Analyse meetresultaten PV-woningen te Heerhugowaard: periode1994 | 
        
            |  | 
        
            | Author(s): | 
        
            |  | 
        
            |  | 
        
            | Published by: | Publication date: | 
        
            | ECN | 1995 | 
        
            |  | 
        
            | ECN report number: | Document type: | 
        
            | ECN-C--95-116 | ECN publication | 
        
            |  | 
        
            | Number of pages: | Full text: | 
        
            | 70 | Download PDF | 
    
    
    
        Abstract:
        Data from measurements, carried out in 1994, on 4 roof-integratedgrid-connected photovoltaic systems of 4 single-family dwellings in
Heerhugowaard, Netherlands, are presented. The yield factors vary from 0.60
to 0.75. The energetic conversion efficiency of the SMA inverters is circa
83% and the energetic conversion efficiency of the so-called Victron
inverters is circa 91%. Also, attention is paid to the different performances
of the three configurations of the installation: SMA inverters in cascade,
SMA inverters parallel, and Victron inverters in stand-alone operation. The
Maximum Power Point Trackers (MPPT) of the SMA inverters appear to be very
sensitive for varying radiations and super-sensitive for high ambient
temperatures of the inverter. Also, the DC-efficiency of the systems with
Victron inverters is not efficient within the radiation area of 50-300 W/m2.
1 figs., 7 tabs., 7 refs., appendices
    
    
        
        
    
    